Jasper Version 2.16.0

    Please contact Cristal Controls technical support before applying an update.
    You may need to adjust settings on your new software version.

Key improvements released in Jasper 2.16.0

Added a Shedding order tab to the Load Shedder page, showing the shedding order of the steps and the state of each step

Added an Overridden tag next to the Actual Power value on the Load Shedder page when the power override is enabled

Added help icons on the Load Shedder page showing the BACnet objects used by the override controls

Added the On Power Loss setting to the load shedder configuration, to choose the action when the power reading is lost (Use Minimum Valid or Hold). New load shedders use Hold by default

Added warnings on the Load Shedder page when the load shedder is not running and when the power reading is lost

Added range checks on typed values in the load shedder configuration and on the Load Shedder page, with the allowed range shown in the help

Added a help icon with the allowed range of the Delay field on the Sequencer configuration page, and enforced the same limit as Jasper

Added the full value as a tooltip on the Text and Link fields of the floor plan configuration

Added summary cards to the Load Shedder page and improved its power bar and state badges

Added a confirmation on the Load Shedder page before large setpoint or power limit changes

Added a duplicate card warning on the Browse Cards page

Improved the Load Shedder page with a confirmation before override changes

Improved the reliability of the load shedder. A misconfigured load shedder, an empty group member or an unavailable Hydro-Québec database no longer stops the shedding

Improved the Jasper Updater, which now runs the web update in the background

Updated PHP to version 8.3.36, lighttpd to version 1.4.85 and OpenSSH to version 9.9_p2-r2 on OS 24.10 devices

Fixed the load shedder not using the power override value in the shedding decisions

Fixed several load shedder calculations, including fractional kW for proportional steps, reversed minimum and maximum power scaling, and a negative manual power limit now treated as no limit

Fixed the effective power limit of the load shedder keeping its old value after the manual power limit was set back to 0 or after a Hydro-Québec event ended

Fixed the handling of Hydro-Québec events with several load shedders

Fixed normal-only load groups being turned on at startup in generator mode

Fixed the load shedder setpoint schedules being duplicated each time the load shedder configuration was saved with more than one load shedder

Fixed all web pages becoming unresponsive under a heavy load of dataserver web service requests

Fixed duplicate cards created by the BACnet Dataserver Discovery page when a card lookup failed

Fixed Jasper pausing for about 4 seconds on each XBee setup retry when the XBee port or module is not available